UPS of PLURYS series
UPS of PLURYS series from 5kVA up to 10kVA are supplied with 1- and 3- phase
input and 1-phase output with possibility set up voltage 220, 230, 240V.
Other parameters:
- UPS use in the control unit a microprocessor of DSP type (Digital Signal Processing)
- a power factor correction on the input (PFC)
- a big crest factor
- a built-in electronic by-pass
- a new charging batteries system - SENSICHARGER
- ECO MODE increase efficiency of the UPS
- wide possibilities of communication, RS 232, RS 485, zero-potential relay contacts, SNMP
Data of important operating parameters (e.g. voltage, failures,
back-up time, etc.) are screened on the display located on the front panel.
If specially ordered, it is possible to provide a remote control
panel and also a manual by-pass with the UPS which enables the UPS intervention
without switching off the load supply.
Also it is possible to order an insulation transformer for a voltaic separation
of the load supply from the mains supply.
UPS can be connected to an external battery module or external
battery charger to prolong the back-up time.
Type |
Power |
Back-up time |
Dimensions w x h x d |
Weight |
UPS |
[kVA] |
[kW] |
[min] |
[mm] |
[kg] |
PLURYS 5 (1f/1f) |
PLURYS 5 |
5 |
3,5 |
10 - 90 |
1-3x(230 x 640 x 620) |
80 - 312 |
PLURYS 6 (1f/1f) |
PLURYS 6 |
6 |
4,2 |
12 - 90 |
1-3x(230 x 640 x 620) |
92 - 368 |
PLURYS 8 (1f/1f)* |
Plurys 8 |
8 |
5,6 |
10 - 50 |
2-4x(230 x 640 x 620) |
145 - 341 |
PLURYS 10(1f/1f)* |
PLURYS 10 |
10 |
7 |
8 - 45 |
1-4x(230 x 640 x 620) |
52 - 346 |
Type |
Power |
Baxk-up time |
Dimensions w x h x d |
Weight |
UPS |
[kVA] |
[kW] |
[min] |
[mm] |
[kg] |
PLURYS 6 (3f/1f) |
PLURYS 6 |
6 |
4,2 |
12 - 90 |
1-3x(230 x 640 x 620) |
95 - 371 |
PLURYS 8 (3f/1f)* |
Plurys 8 |
8 |
5,6 |
10 - 50 |
1-4x(230 x 640 x 620) |
47 - 341 |
PLURYS 10 (3f/1f)* |
Plurys 10 |
10 |
7 |
8 - 45 |
1-4x(230 x 640 x 620) |
52 - 346 |
Note:
* standard version ( back- up time 10 min.) UPS of PLURYS series from 8 kVA up to 10kVA
consists of two battery modules.
Back-up time depends on used battery modules. If you require longer back-up time, please, contact producer.